Electric Motor Voltage Quality Problems
From the U.S. Department of Energy's Publication, Energy Matters
By Doug Dorr, EPRI Solutions Inc., and Philip Lim, Memphis Light Gas & Water
Voltage nameplate ratings found on many alternating
current (AC) motors and drives can be a source of confusion
for utilities and their industrial customers. The confusion
stems from the voltage range in which a particular motor
may be operated safely. Additionally, voltage unbalance is
known to create premature failure of heavily loaded motors
if they are not properly derated. This article, the second
and final article in our series that began with the Winter
2005 issue, discusses standards associated with AC
induction motors and their nameplates and details a range
of voltage quality issues that may warrant a
problem-solving investigation.
AC induction motors support nearly every facet of
industrial production. These workhorses of industry have been
estimated to be part of the utilization of over half of the
world's electric power generation. The AC induction motor
typically has an inherent amount of tolerance to variations
in utilization voltage as specified by the National
Electrical Manufacturers Association (NEMA), however, utility
power quality engineers can spend a great deal of time simply
answering customer questions regarding proper utilization
voltage for a given motor. While the motor can be operated
with variations in the nominal voltage, it is important to
understand all of the potential impacts on the supported
process as well as on the motor itself.
The voltage quality related factors that tend to create
the most serious problems in the field (and the most
confusion) are nominal utilization voltage that does not
match the motor nameplate, proper voltage sag ride through
protection for the motor control circuitry, and
phase-to-phase voltage unbalance. With these factors in mind,
a systematic approach to investigating and resolving
potential problems can be formulated.
Nominal Utilization Voltage
The U.S. standard for motor nameplate information can be
found in the NEMA Standards Publication MG 1-2003: Motors and
Generators. Motors meeting the criteria contained in the NEMA
standard will operate satisfactorily within plus-or- minus
10% of the rated voltage. For example, if the voltage rating
on the motor nameplate is 460 volts, that particular motor
should operate safely when the utilization voltage is between
414 and 506 volts. However, as the voltage changes-even
within the NEMA range-so will the torque, temperature,
current, motor speed, and other motor characteristics.
Additionally, any increase in operating temperature may
accelerate the deterioration of the motor's electrical
insulation system. Studies of operating temperature and its
effect on insulation life suggest that a rise in steady-state
operating temperature of 10 degrees Celsius can reduce
insulation life by 50% or more. Table 1 shows some common
motor voltages and the range in which the motors may be
operated. Table 2 shows the effects of voltage
variations on three-phase motors.
Table 1. Utilization Voltage Ranges for Induction Motors (from NEMA Motors and
Generators Standard MG-1-1993)
| Rated Motor Voltage (V) |
Rated Motor Frequency (Hz) |
Minimum Motor Voltage (90%) |
Maximum Motor Voltage (110%) |
| 110 |
60 |
99 |
121 |
| 115 |
60 |
104 |
126 |
| 200 |
60 |
180 |
220 |
| 208 |
60 |
188 |
228 |
| 220 |
50 |
198 |
242 |
| 230 |
60 |
207 |
253 |
| 300 |
60 |
270 |
330 |
| 380 |
60 |
342 |
418 |
| 440 |
50 |
396 |
484 |
| 460 |
60 |
414 |
506 |
| 575 |
60 |
518 |
632 |
| 2300 |
60 |
2070 |
2530 |
| 4000 |
60 |
3600 |
4400 |
| 4600 |
60 |
4140 |
5060 |
| 6600 |
60 |
5940 |
7260 |
* The plus-or-minus 10%
voltage rating for AC induction motors assumes that
the motor is operated at the nominal frequency. If
the frequency is not the same as the nameplate
frequency and in particular when 60-hertz motors are
operated on 50-hertz systems, the sum of the percent
of voltage difference and the percent of frequency
difference from the nameplate ratings must not
exceed10%. Values are approximate and voltages at or
slightly above nominal are preferred for lower
operating temperatures and higher starting
torques.
Table 2. General Effect of Voltage Variations on Characteristics of Induction
Motors (from IEEE Std 141-1993)
| Motor Characteristic |
Voltage Variation |
| 90% of Nameplate |
110% of Nameplate |
| Starting and Maximum Running Torque |
-19% |
+21% |
| Percent Slip |
+22% |
-19% |
| Full-Load Slip |
-0.2% to -1.0% |
+2.0% to +1.0% |
| Starting Current |
-10% |
+10% |
| Full-Load Current |
+5% to +10% |
-5% to -10% |
| No-Load Current |
-10% to -30% |
+10% to +30% |
| Temperature Rise |
+10% to +15% |
-10% to -15% |
| Full-Load Efficiency |
-1% to -3% |
+1% to +3% |
| Full-Load Power Factor |
+3% to +7% |
-2% to -7% |
| Magnetic Noise |
Slight Decrease |
Slight Increase |
Voltage Unbalance
The second voltage quality related issue that the NEMA
standard addresses is voltage unbalance. Unbalanced motor
voltages may cause a current unbalance that in turn increases
the operating temperature and energy losses of the motor. A
voltage unbalance can magnify the percent current unbalance
in the stator windings of a motor by as much as 6-10 times
the percent voltage unbalance. When the voltage unbalance is
more than 1%, derating the motor will help to mitigate the
effects of the voltage unbalance. If the voltage unbalance
exceeds 5%, it is not advisable to operate the motor at
all-even when the motor has been derated. When a voltage
unbalance exceeds 3%, the root cause of the unbalance should
be identified and remedied. In cases where motor failures are
occurring repetitively and the unbalance is greater than 1%,
it may be prudent to investigate and resolve the root cause
of the unbalance.
Voltage unbalance must be treated separately from
unusually low or high voltage conditions for three phase
motors. As a matter of fact, both conditions in tandem would
be a worst case condition for any motor, however there are a
couple of sanity checks that can be performed to alleviate
concerns (even when both voltage related problems are
present). Provided that the motor nameplate current is not
exceeded on any of the phase conductors and provided the
actual motor speed is greater than or equal to the nameplate
revolutions per minute (RPM), one can assume that detrimental
affects on the motor are minimal. The condition under which
the preceding statement would hold true would be that of a
lightly (<50%) loaded motor. This is explained in more
detail below, in the section on remedying voltage
problems.
Voltage Related Symptoms
Symptoms of motor problems related to either voltage
unbalance or to voltages not matching the nameplate rating
are not always easy to diagnose because both the utility and
facility distribution voltages vary as the system load and
other system characteristics vary. Measuring the steady-state
voltage at accessible points in the motor circuit is a very
good way to determine whether a potential for voltage
problems exists. A few symptoms that may trigger such an
investigation include:
- Unusually high numbers of motor failures
- Not getting the expected motor life between rewinds
- Unexplained motor trips
- Motors that are more sensitive to voltage sags than other electrical process equipment
- Difficulty getting a specific motor started
- Nuisance tripping of a motor-protective device.
Additional possibilities beyond operating voltage and
voltage balance can cause these symptoms. But the list
provides a good starting point for deciding whether to
conduct a voltage investigation.
Problem Solving Investigation
When a voltage quality problem with a motor is suspected,
a proven procedure for investigating the problem is as
follows:
Step 1.
Find out enough information about the problem to determine
whether the problem is isolated to one motor circuit or is
common to the entire facility. This will help determine where
to measure and possibly whether the source is internal or
external. Develop a worksheet similar to the one shown in
Table 3 to record circuit voltages (phase to phase/line to
line for all phases), phase currents (using a true-RMS meter
to detect the contribution of harmonics, if present),
calculate unbalances and to record motor nameplate voltage,
current, and revolutions per minute (RPM).
Step 2.
Measure the voltage and current at accessible connection
locations between the source transformer and the motor
terminals. If the motor is three-phase, record voltage and
current measurements for all three phases. If possible,
obtain the measurements with the motor not running and also
with the motor operating at its maximum steady-state loaded
condition. Record the measured values in separate copies of
the worksheet. For loads such as a chiller motor, it may also
be useful to record steady-state voltages and currents at
loading conditions other than full load. Don't forget to
measure the coil voltages at the motor control circuit. It is
very common to find that the motor tripping problems are
associated with sags and low voltages at the control relay
and starter coils for AC induction motors.
Step 3.
If the motor is three-phase, calculate the percent voltage
unbalance using the following method. First, average the
three voltages (the sum of phase A to B, phase B to C, and
phase C to A divided by three). Then, select the
phase-to-phase voltage that deviates most from the average.
Determine the difference between the average voltage and the
maximum deviation from the average. To determine the percent
voltage deviation, multiply the difference times 100, and
divide that number by the average. For example, if the
measured voltages are 462, 465 and 447 volts: 461 + 465 + 447
= 1373; 1373/3 = 458. The greatest variation is 11 volts (458
- 447 = 11). 100 x 11/458 = 2.4% voltage unbalance. Repeat
the calculation for percent current unbalance. For every 1%
voltage unbalance, expect 6-10% current unbalance. Record
both unbalances in the worksheet.
Step 4.
If steps 1 through 3 reveal either 1) a motor current
above the rated current, 2) a voltage unbalance above 1% that
is not present when the motor is shut off, or 3) a
utilization voltage outside the appropriate voltage range in
Table 1, do the following before continuing:
- Inspect all motor circuit elements downstream from the
mains disconnect, including contactors, connectors, and
conductors.
- Ensure that all connectors have tight low-impedance
connections, including those inside the motor connection
box.
- Ensure that the connectors are compatible with the
metallic conductor type used.
- Ensure that motor contactors are not seriously worn or
deteriorated to a point where high resistance is
present.
- Ensure that the motor circuit conductors are properly
sized and all of the same conductor material and in similar
condition.
If the voltage unbalance is greater than 3% while the
motor is not running, then contact your local utility to
determine the cause of the unbalance. If one or more problems
were found from the above inspections resolve the problems
and then complete Steps 1 through 4 before continuing to Step
5.
Step 5.
If Steps 1 through 4 reveal a low voltage, high voltage,
or voltage unbalance greater than 1%, consider the following
remedies:
If the steady-state voltage is too high or too low:
If the motor utilization voltage is higher or lower than
the plus-or-minus 10% specification, or if the user desires
that the motor operate closer to the nameplate nominal
voltage, several acceptable methods exist for increasing or
decreasing the supply voltage. If you decrease the
utilization voltage, remember that as the utilization voltage
decreases, the susceptibility of motor starters and control
circuits to voltage sags will increase.
Utilization voltages can be adjusted via no-load tap
changers on existing step-down service transformers. However,
changing these taps interrupts the power to all transformer
loads. Therefore, entire processes within a facility must be
shut down during tap changes. Additionally, changing the taps
of the service transformer will affect terminal voltages
throughout the plant, potentially changing voltages at
equipment that do not require a different voltage.
Step-up or step-down transformers can also be used to
adjust utilization voltages. Some transformers, such as the
constant-voltage transformer, can also mitigate the effects
of voltage sags on motor-control circuits. Another way to
adjust a utilization voltage is to boost or buck the voltage
with an autotransformer. The buck-boost transformer can be
field-connected to increase (boost) or decrease (buck) a
utilization voltage from 5-20%, depending on the way the
primary and secondary windings are connected. Because only
the secondary windings carry current in an autotransformer
configuration, a buck-boost transformer may be rated as much
as 10 times lower than a fully isolated two-winding
transformer. And although buck-boost transformers are
single-phase, they can be applied to most three-phase
equipment by matching three single-phase transformers.
Caution: the transformer impedances must all match when
applying single-phase transformer in a 3-phase
configuration.
If the voltage unbalance is high:
The root cause of the unbalance condition must be
identified and the percent unbalance evaluated to determine
what to do. There are a large number of possible causes for
voltage unbalance, for example utility supply voltage
unbalance, unbalanced single phase loads, high impedance
connections, and malfunctioning voltage regulators. In many
cases, the checklist from Step 4 above may uncover the root
cause of the unbalance and lead to a fairly inexpensive
solution. If the unbalance cannot be traced to an internal
distribution element or to unbalanced single-phase loads in
the facility, the local utility may need to assist by
evaluating the percent unbalance of the distribution system,
and the condition of the voltage regulation devices.
For a voltage unbalance of less than 1%, no remedial steps
are necessary unless nuisance tripping or trouble during
startup is associated with the unbalance. As the percent
unbalance increases, the likelihood of problems increases.
The NEMA standard for voltage unbalance states that a motor
will operate satisfactorily at its rated load with a voltage
unbalance up to one percent at the motor terminals. The
American National Standards Institute (ANSI)/Institute of
Electrical and Electronics Engineers (IEEE) C84.1 standard
for nominal voltages implies that an adequately designed
power system can have up to a 3% inherent voltage unbalance.
However, if measurements at the motor terminals indicate more
than a 1% voltage unbalance, the motor should be derated
according to Figure 2.
| |
 |
|
The derating curve in the figure can be applied to small
and medium motors to minimize overheating. The curve assumes
that the motor is already operating at its rated load.
However, many motors do not operate at the rated load and are
thereby in effect already derated.
A Motor Failure Case Study
An industrial customer called the local utility to report
that the plant was experiencing excessive motor failure for
no apparent reason. There was no history of motor failures so
a utility voltage complaint investigator was dispatched to
look into the problem. The customer's power is fed from a
three-phase 750 kilovolt-ampere (kVA), 480Y/277 volt
transformer. Because the motor failures were occurring on
multiple circuits, the initial measurements were taken at the
main service panel. Using the steps in the investigation
procedure, a definite voltage unbalance was discovered inside
of the facility. The measured voltages were:
- Phase A to B: 469.5 V
- Phase B to C: 503.3 V
- Phase C to A: 490.4 V
The average voltage from these readings was calculated to
be 487.7 V, with the maximum voltage deviation from this
average being 18.2 V (487.7-469.5)
The voltage unbalance at this facility was calculated to
be 3.7% [(Maximum Voltage Deviation from the Average/Average)
* 100]. This unbalance is above the level where we might
expect internal loads and circuits to be the source of the
problem.
Current measurements were then taken at the riser pole on
the 12.47 kilovolt (kV) side (the feed to the customer's pad
mounted 750 kVA transformer). The measured currents were:
- Phase A = 14.4 A
- Phase B = 16.1 A
- Phase C = 17.7 A
Using the formula [(Maximum Current Deviation from
Average/Average)*100] the current unbalance for the facility
was calculated to be 10.6%.
With the measured results in hand, a decision was made to
focus the investigation on the utility source. An
investigation of the circuit feeding the facility indicated
that potential contributors to the voltage unbalance could
either be a line voltage regulator (located 1.6 miles from
the facility) or a set of power factor correction capacitor
banks farther away. The voltage unbalance problem was
explained rather quickly when the investigator read the
settings on the line voltage regulator. The setting for
A-phase setting was at position 12 buck (lower), B-phase
setting at position 4 boost (raise), and C-phase setting at
position 8 boost (raise). The voltage unbalance was caused by
the malfunctioning of phase A and C regulators. Repairing the
malfunctioning voltage regulators solved the problem. While
this problem was fairly easy to resolve, the steps described
in the investigation section proved useful in identifying the
root cause.
A Motor Failure at a Polymers Plant
A polymers processing plant was experiencing an
unacceptable number of process dropouts that plant engineers
felt were electric power-induced problems. Plant personnel
estimated the losses to be greater than $1 million a year
with an average of 15 process dropouts annually. The plant
was fed electrically from a 12.6 kV circuit prone to numerous
types of problems ranging from cars hitting poles to animals
faulting the power lines.
An investigation of the critical components at this plant
indicated the majority of dollar losses were experienced when
kill agents were dumped into the chemical reactors to stop
the exothermic (heat generating) reaction. These kill agents
are only used in an emergency if facility cooling water is
lost due to the motors for the pumps and fans for the cooling
process either failing or tripping off line. The result is
approximately two weeks' worth of reduced grade (or out of
spec) product while the residual kill agent works its way out
of each stage of the process.
After discussing the problem with plant personnel it was
determined that the kill agent would not have to be injected
into the reactor if three critical cooling process components
were maintained. These were the instrument control air
compressors, the agitator motors for the reactor vessels and
the cooling tower fans and pumps. At this particular plant,
the voltage balance and nominal operating voltage level at
the equipment were adequate, and it was suspected that
voltage sags tripping the controls were the source of the
problem.
Reviewing the utility's power quality data for voltage
variations experienced at the substation feeding the plant
indicated that about 90% of the sags were less severe than
50% of nominal voltage and did not last longer than about
one-third of a second (20 cycles). Based on this information,
it was clear that simply holding the critical process
elements in for a half second or so would solve this costly
problem.
Control circuit testing with a portable voltage sag
generator confirmed the sensitivity of the control relay and
motor starter coils to voltage sags. The facility's
electrical maintenance group was provided with an overview of
the identified problem and given a range of solutions that
included pneumatic relays, constant voltage transformers and
coil hold-in devices. Once they understood that holding in
these processes momentarily would have no detrimental impact
on plant or personnel safety they were eager to get the
problem solved. The solution was a coil hold-in device that
could be mounted in a standard relay socket next to the
sensitive relays and starters. The coil hold-in device is
connected between the AC source voltage and the coil of the
relay or starter to be protected and substantially improves
voltage-sag and tolerance. During a voltage sag condition,
the device maintains a current flow through the coil
sufficient to hold in the contacts. These coil hold-in
devices are designed to protect the circuit from voltage
sags, but are also designed to drop the circuit out if power
is interrupted or if an emergency stop signal is applied.
Because the compressor required manufacturer approval
before making modifications to the controls, it was
recommended that the manufacturer be supplied with the range
of options along with an explanation of the half-second hold
in objective. The compressor manufacturer could then propose
the best solution for their specific brand that would enable
the facility to meet the hold in objective.
Motor power quality is a topic of concern to industrial
customers and utility personnel alike. With a proper
understanding of the impacts voltage quality may have on AC
induction motors and a systematic investigative approach,
most problems can be effectively and efficiently solved. As
with nearly all power quality related problems, the solutions
are simply a matter of having the proper tools and the know
how to identify and isolate the root cause of the
problem.
Of course having access to a device that can generate
voltage sags on demand instead of waiting months for the next
event to occur certainly helps out too! - U.S. Department of Energy